Chief’s Regulation 4 Testing Frequency Schedule

Under LAFD Chief’s Regulation 4, each fire and life-safety system in a Los Angeles building has its own testing interval. Most systems, including methane gas detection, are tested every year. Standpipes, automatic sprinklers and full-flow pressure reducing valves also need a five-year test. Here is the complete Reg 4 testing frequency schedule and how to keep your building on it.

Chief’s Regulation 4 Testing Frequency Table

SystemFrequencyNotes
Basic fire warning systems1 yearFire alarm systems
Complex fire warning systems1 yearIncludes high-rise fire/life-safety systems
Central station signaling systems1 yearSupervising station monitoring
Smoke management systems1 yearSmoke control, pressurized stair shafts
Automatic elevators1 yearPhase I and Phase II emergency operation
Emergency generator and lighting systems1 yearIncludes stored electrical energy (battery) systems
Fire doors (all types and occupancies)1 yearAutomatic-closing fire assemblies
Fire escapes1 year
Fire pumps1 year
Pressure reducing valves (PRVs), partial flow1 yearHose connection PRVs
Pre-action, deluge and dry pipe systems1 yearTested annually
Methane gas detection and mechanical ventilation1 yearAnnual test under LAMC 91.7106 and Reg 4, Section 4J
Class I, II, III, combined and Class H standpipes5 years
Automatic fire sprinkler systems5 years
PRVs, full flow5 years

Intervals are from the LAFD Chief’s Regulation 4 page and, for methane systems, Section 91.7106 of the Los Angeles Building Code. Always confirm current requirements for your building with LAFD or your Fire Inspector.

Annual Tests: The Anniversary Month

Annual Reg 4 tests are generally a full test of the whole system performed in the same month each year, known as the system’s anniversary test date. Keeping to the same month makes compliance easy to track for both the owner and the Fire Department. If a test slips, bring the system back on schedule rather than letting the gap grow.

Five-Year Tests

Standpipes, automatic sprinkler systems and full-flow PRVs need a more involved test every five years. These tests often require flowing water and coordination with building management, so plan them well ahead. A building with a five-year test due still needs its regular annual tests on the other systems that year.

Methane Gas Detection: Every Year

For buildings in a Los Angeles Methane Zone with an active methane mitigation system, the gas detection sensors, alarm, control panel and extraction fans are tested every year by an LAFD-certified Gas Detection tester. This is separate from the fire alarm test, even when the same company services both. Read the full guide to Reg 4 methane gas detection system testing.

Deadlines After Each Test

  • 7 days: the certified tester files the results on Fire Department-approved forms. LAFD directs filing through The Compliance Engine; high-rise buildings (75 feet or taller) must use it, and other buildings follow their Fire Inspector’s directions (see LAFD’s Compliance Engine FAQs).
  • 30 days: defects must be corrected right away and no later than 30 days after the initial test, then the system is retested.

Building a Reg 4 Testing Calendar

  1. List every system in the building that appears in the table above.
  2. Pull the last test report for each and note its anniversary month.
  3. Mark any five-year tests coming due.
  4. Book LAFD-certified testers for each system type at least a month ahead.
  5. Keep reports, repair records and permits on site for Fire Department inspections.

Owners who have several systems tested by different companies often group annual tests into the same month to cut down on tenant disruption.

FAQs

How often is a Reg 4 test required?

Most systems every year. Standpipes, automatic sprinkler systems and full-flow PRVs also every five years.

How often must a methane gas detection system be tested in Los Angeles?

Every year, by a tester holding an LAFD Gas Detection certification.

What if my building missed a Reg 4 test?

Schedule the overdue test with a certified tester as soon as possible and keep the report. If your Fire Inspector has issued a notice, follow its directions and deadlines.